Technical description
The M8725 display was specially designed for hazardous
areas (IIC). It replaces analog needle displays with or
without limit contacts.
The instruments are available for either horizontal or
vertical mounting. Values between -1999...+1999 digits
can be displayed with an input signal of 4...20mA.
Decimal point and input range are configured in the
factory to customer needs.
The display is available in two different sizes:
½"(13mm) or 1"(27mm). Due to the display size, only the
following variants are possible:
-Vertical mounting with 13mm display, with and without
digital limit contacts. Type M8725-GV and M8725-V
-Horizontal mounting with 13mm display, with and without
digital limit contacts. Type M8725-GH and M8725-H
-Horizontal mounting with 27mm display, with and without
limit contacts. Type M8725-GHA and M8725 -HA
The limit contacts are adjustable over the entire range
and switch NAMUR-signals when they exceed the limit
values. Both contacts can be factory configured to N/O
or N/C. Both contact outputs are galvanically separated
from the measuring signal by optocouplers. The display
is powered by the measuring signal of 4...20mA through
which a 3,8 to 4V voltage drop occurs. With input
signals of 0...20mA a certified power supply is
necessary. For example, power supply Type WG17R of Knick
Berlin.
Example: Temperature display and control of a vessel
within the hazardous area. Input 4...20mA, display range
-30,0...70,0ºC, Outputs = N/C.
|