Technical description
The M2029-A and M2029-AR are panel mounted display units
to display physical units as: pressure, weight, RPM,
temperature, voltage, current, %, ppM etc. Input
signals are voltages or currents. An isolating switching
power supply is used to galvanically isolate between
supply and signal. Two optional, floating alarm contacts
for heavy loads are available.
The small outlines, W x H x D of 48 x 24 x 75mm makes
the instrument useful on highly populated panels.
A 4-digit LED display shows the actual value and
setpoints or alarm values in the range of -1999 to 9999
units.
All settings as alarm values, hysteresis, range and
operating mode of the floating contacts can be made with
a link cable, connected to a personal computer or a
laptop.
Both alarm contacts can also be programmed with two tiny
push button switches behind the front panel.
Example:
The pressure is measured in a process vessel by means of
a pressure transducer with an output signal of 4...20mA
corresponding to a pressure of 1...10bar.
The pressure is displayed in the form of
1.00...10.00bar. One of the two alarm contacts is set at
7.00bar to signal high pressure to the process computer.
|